- Guaranteed tightness with enveloping seal and anti-creep ring.
- Corrosion resistance: 250 Micron epoxy coating Flanges & Internal part.
- Simple and quick installation.
- Angular deviation ±4°.
- Simple bolting.
Simple and quick implementation:
- Angular deviation ±3.5°.
- Simple bolting.
Compliance with standards:
- NF EN 1092-2: 1997: Flanges and their assemblies. Part 2: Cast iron flanges.
- NF EN 12842: 2012: Ductile iron fittings for PVC & PE and or PVC-BO pipeline systems
- ISO 2531: Ductile iron pipes, fittings and accessories.
- ISO 7005-2: 1988: Metal flanges, cast iron flanges.
- ISO 7483: Dimensions of joints to be used with ISO 7005 flanges.
Approval:
- ACS (Attestation of Sanitary Conformity).
Note:
- The anchoring system takes up the forces due to the hydraulic pressure within the limit of the PFA. It is not designed to withstand the mechanical forces of the pipes.
- Vertical upward mounting not recommended
Characteristics:
• Range:
- For PVC-U, PVC-BO (Request the list of compatible tube manufacturers) and PE 80 or PE 100 PN16, DN 50 to 200.
- For pipes with PVC external diameters.
• PFA 16
• Flange drilling:
- ISO PN 10/16
- Double drilling ISO PN 10 / ISO PN 16 for DN 200.
• Operating temperature: +0°C to +60°C.
Applications:
• Water distribution networks
• Fire protection networks
• Irrigation networks
• Fully self-stopped network or vertical piping, see instructions for use assembly.
Tests:
- Watertightness test according to ISO 2531 and NF EN 14525.